Home/Other Calculators & Tools/Voltage Drop Calculator

Voltage Drop Calculator

Free cable voltage drop calculator · No sign-up · Runs entirely in your browser

Estimate the voltage lost along a cable run for 12V, 24V, 230V and three-phase systems in copper or aluminium — and see how far you can run before it matters.

Circuit Details
⚡ AS/NZS 3000: Max allowable voltage drop = 5% of supply voltage (230V = 11.5V max)
System voltage
Current (A)
Cable length (one-way)
m
Cable size (mm²)
Conductor material
Result
Voltage Drop
ParameterValue

Australian Cable Sizing (AS/NZS 3008)

The AS/NZS 3008 standard governs cable selection in Australian electrical installations. Key factors: current-carrying capacity (ampacity), voltage drop, and fault current ratings. Maximum voltage drop for final subcircuits is 5% of nominal supply voltage.

⏱️ Last reviewed: 26 July 2026 · Written and reviewed by Mohsin Iqbal under our editorial policy and calculation methodology.
This is an estimate, not a compliance check. It calculates the drop in one cable run at 20 °C using resistance only. Australian compliance is assessed on the cumulative drop across the whole installation, using tabulated values at operating temperature. In Australia, mains electrical work must be carried out by a licensed electrician — this page is educational.
📖 Approx. 14 min read🇦🇺 AS/NZS 3000 context🔄 Updated 26 July 2026

On this page

  1. What Voltage Drop Is
  2. Where the Voltage Goes
  3. The Formula
  4. How to Use This Calculator
  5. Copper vs Aluminium
  6. Typical Current Draw
  7. Worked Example 1: 12 V Caravan Circuit
  8. Worked Example 2: 24 V Solar Run
  9. Worked Example 3: 230 V Household Circuit
  10. How Australia's 5% Limit Actually Works
  11. Quick Target Reference
  12. Cable Length Limits at 12 V
  13. Cable Sizes You Will See
  14. How to Reduce Voltage Drop
  15. Common Mistakes
  16. Frequently Asked Questions
  17. Size for the Drop, Not Just the Current

🔑 Key Takeaways

What Voltage Drop Is

Cable is not a perfect conductor. It has resistance, and pushing current through resistance costs voltage — so the appliance at the far end of a run always sees slightly less than the supply. That difference is the voltage drop.

It is Ohm's Law applied to the cable itself. The cable becomes an unintended resistor in series with your load, and the voltage it consumes is V = I × Rcable. Everything else on this page follows from that. For the underlying relationships, see our Ohm's Law calculator.

ConsequenceWhat actually happens
MotorsRun hotter and produce less torque. A 5% voltage deficit can cost roughly 10% of torque output
LightingPerceptible dimming, and shortened lamp life in some types
ElectronicsNuisance resets and dropouts, particularly in 12 V systems
Heating elementsReduced output — power falls with the square of voltage
The cable itselfThe lost voltage becomes heat in the conductor. It is wasted energy you pay for

Where the Voltage Goes

Using the caravan example below — 12 V, a 15 A fridge, 6 m of 6 mm² copper each way:

How voltage is lost along a cable run A 12 volt battery supplies a 15 amp fridge through 6 metres of 6 square millimetre copper cable each way. The cable has a total loop resistance of 0.035 ohms. It consumes 0.525 volts, which is released as 7.9 watts of heat in the conductor, so the fridge receives 11.47 volts instead of 12 volts — a 4.4 per cent drop. SOURCE 12.00 V battery active — 6 m of 6 mm² copper 15 A flows this way and returns this way — which is why the formula doubles the length negative / return conductor 7.9 W lost as heat in the cable loop resistance 0.035 Ω AT THE LOAD 11.47 V fridge 0.525 V lost in the cable — 4.38% of a 12 V supply

The cable is not a wire with a problem — it is behaving exactly as a resistor should. Those 7.9 watts are real energy leaving your battery and warming the conductor instead of running the fridge, and they scale with the square of current.

The Formula

DC and single phase:   Vdrop = 2 × I × ρ × L ÷ A
Three phase:           Vdrop = √3 × I × ρ × L ÷ A

I = current (A)  ·  L = one-way cable length (m)  ·  A = conductor cross-section (mm²)
ρ = resistivity: copper ≈ 0.0175, aluminium ≈ 0.0282 Ω·mm²/m
Why 2 for single phase but √3 for three phase. In a single-phase or DC circuit the current travels out along the active and back along the neutral, so it passes through two conductor lengths — hence the 2. In a balanced three-phase circuit the three phases return through each other and there is no significant neutral current, so the line-to-line drop works out to √3 (about 1.732) rather than 2. Using 2 for a three-phase circuit overstates the drop by about 15.5%.

Enter the one-way length — the distance from source to load, not there and back. The formula already accounts for the return path.

How to Use This Calculator

  1. Choose your system voltage. The percentage is calculated against this figure, so 12 V results look very different from 230 V ones.
  2. Enter the current the circuit will actually carry, not the breaker rating.
  3. Enter the one-way cable length from source to load.
  4. Pick the conductor size and material. Doubling the size roughly halves the drop.
  5. Read the result as an estimate. If it is close to your limit, upsize — see the caveats below before treating any figure as compliance.
Three things this calculation does not include. It uses resistance at about 20 °C, but a loaded cable runs hotter and its resistance rises with temperature. It ignores reactance, which matters on larger AC cables. And it covers one run, whereas Australian limits apply to the whole path. Each of these pushes the real figure higher than the estimate, so treat a result near your limit as a fail.

Copper vs Aluminium

CopperAluminium
Resistivity (Ω·mm²/m)~0.0175~0.0282
Drop for the same sizeBaselineAbout 61% more
Size needed for equal dropBaselineRoughly 1.6× the cross-section
WeightHeavierAbout one third the weight
Typical useAlmost all domestic and general wiringLarger submains, overhead and utility runs
TerminationsStraightforwardNeeds compatible lugs and correct preparation

Aluminium is cheaper per amp delivered and much lighter, which is why it appears in large submains and overhead work. For the small runs most people are calculating — caravans, solar, sub-boards to a shed — copper is almost always the practical choice.

Typical Current Draw

You need a current figure before you can calculate drop, and wattage is usually what is printed on the appliance. Divide watts by the system voltage.

230 V applianceTypical powerCurrent
LED downlight8 W0.03 A
Laptop charger65 W0.28 A
Refrigerator (running)250 W1.09 A
Water pump750 W3.26 A
Microwave1,200 W5.22 A
Kettle2,200 W9.57 A
Split-system air conditioner2,500 W10.87 A
Electric oven3,000 W13.04 A
EV charger (single phase)7,400 W32.17 A
12 V loadTypical powerCurrent
LED strip12 W1.00 A
Diesel heater30 W2.50 A
12 V compressor fridge55 W4.58 A
Water pump60 W5.00 A
600 W inverter at full output~700 W drawn58.33 A
Two things this table cannot show you. Motors, compressors and pumps draw a large surge on startup — often several times running current for a moment — which is why they can dim lights briefly and why cable and protection are not sized on running current alone. And look at that last row: a modest 600 W inverter pulls nearly 60 A from a 12 V battery. That single figure explains why inverter cables are enormous and kept as short as physically possible.

Worked Example 1: 12 V Caravan Circuit

A 12 V fridge drawing 15 A, 6 m of cable from the battery, 6 mm² copper.

StepWorkingResult
Cable resistance (one way)0.0175 × 6 ÷ 60.0175 Ω
Voltage drop2 × 15 × 0.01750.525 V
As a percentage0.525 ÷ 124.38%
Voltage at the fridge12 − 0.52511.48 V
Upsized to 10 mm²2 × 15 × 0.01050.315 V (2.63%)
This is why 12 V systems catch people out. Six metres of 6 mm² cable sounds generous, and it still loses 4.4%. Many 12 V appliances and battery chargers behave poorly below about 11.5 V, so the practical target for 12 V work is usually 3% or less, not 5%. Upsizing one step to 10 mm² fixes it.

Worked Example 2: 24 V Solar Run

A solar array delivering 20 A over a 15 m run to the charge controller, 6 mm² copper.

Vdrop = 2 × 20 × 0.0175 × 15 ÷ 6 = 1.75 V = 7.29% of 24 V

Well outside any sensible limit, and every one of those volts becomes heat in the cable rather than charge in the battery. Doubling to 16 mm² brings it to 0.66 V (2.73%). This is the classic solar mistake: sizing cable for current-carrying capacity alone, when on long runs it is voltage drop that governs.

Note what 24 V buys you. The same power at 24 V draws half the current of a 12 V system, and drop scales directly with current — so doubling system voltage halves the drop for identical cable. It is the reason larger off-grid systems run at 24 V or 48 V rather than 12 V.

Worked Example 3: 230 V Household Circuit

A 16 A load 35 m from the switchboard on 2.5 mm² copper.

StepWorkingResult
Voltage drop2 × 16 × 0.0175 × 35 ÷ 2.57.84 V
As a percentage7.84 ÷ 2303.41%
Upsized to 4 mm²4.90 V (2.13%)
3.41% looks compliant. It may not be. That figure is for this run alone. The consumer mains and any submain feeding this board have already consumed part of the 5% budget before this cable starts. If the upstream path has used 2%, the total is 5.4% and the installation fails — even though this cable "passed". This is the single most common voltage drop error, and it is the reason a per-cable calculator cannot tell you whether an installation complies.

How Australia's 5% Limit Actually Works

The AS/NZS 3000 Wiring Rules set a maximum voltage drop of 5% of nominal supply voltage, measured from the point of supply to any point of utilisation. The critical word is cumulative. It is a budget for the entire path, shared between every segment.

Nominal voltage5% budgetComment
230 V single phase11.5 VShared across mains, submains and final subcircuit
400 V three phase20.0 VLine-to-line. Older equipment is often still labelled 415 V
24 V DC1.2 VNot covered by the Wiring Rules, but a useful design target
12 V DC0.6 VVery tight — most designers work to 3% instead

Because the budget is shared, designers allocate it in advance. A common domestic approach is roughly 1.5% for consumer mains, 1.5% for submains and 2% for final subcircuits; another is a simple 2.5% / 2.5% split between submain and final circuit. The allocation is a design decision, not a fixed rule.

Two further points worth knowing. The Wiring Rules separately suggest keeping lighting circuits to around 3% to avoid visible dimming — a recommendation rather than a requirement. And formal cable selection under AS/NZS 3008 does not use the simple formula on this page: it uses tabulated millivolt-per-amp-per-metre figures at the conductor's maximum operating temperature, which include reactance as well as resistance. Those tables will give a higher figure than this estimate, which is why this calculator is a design aid rather than a compliance tool.

Quick Target Reference

Two different things get conflated here, so it is worth separating them. The regulated figure is a cumulative limit for a whole installation. The design target is what experienced installers aim for on a single run so the cumulative total stays inside it.

SystemRegulated limitPractical target per runWhy
12 V DCNot covered by the Wiring Rules≤3% (0.36 V)5% is only 0.6 V; many 12 V devices misbehave below ~11.5 V
24 V DCNot covered≤3% (0.72 V)Same reasoning, with twice the headroom in volts
48 V DCNot covered≤3% (1.44 V)Common in larger off-grid and telecoms systems
230 V single phase5% cumulative (11.5 V)≤2–2.5% per segmentLeaves budget for mains and submains upstream
400 V three phase5% cumulative (20 V)≤2–2.5% per segmentSame cumulative budget, shared across the path
Lighting is the exception worth knowing. The Wiring Rules separately suggest keeping lighting circuits nearer 3% to avoid perceptible dimming. It is a recommendation rather than a requirement, but it is why lighting circuits are often sized more generously than the current alone would justify.

Cable Length Limits at 12 V

Maximum one-way run for a 3% drop on 12 V copper. This is the table caravan, 4WD and small solar builders need most.

Conductor5 A10 A15 A20 A30 A
1.5 mm²3.1 m1.5 m1.0 m0.8 m0.5 m
2.5 mm²5.1 m2.6 m1.7 m1.3 m0.9 m
4 mm²8.2 m4.1 m2.7 m2.1 m1.4 m
6 mm²12.3 m6.2 m4.1 m3.1 m2.1 m
10 mm²20.6 m10.3 m6.9 m5.1 m3.4 m
16 mm²32.9 m16.5 m11.0 m8.2 m5.5 m
25 mm²51.4 m25.7 m17.1 m12.9 m8.6 m

Copper at about 20 °C, 3% of 12 V. Halve these lengths for a 1.5% target; roughly double them for a 24 V system at the same power.

Look at how short these runs are. A 20 A load on 6 mm² is out of spec past about three metres. This is why heavy 12 V loads — inverters, winches, fridges — use very large cable over what look like trivial distances, and why running them at 24 V or moving the battery closer often beats upsizing the cable.

Cable Sizes You Will See

These are the sizes commonly encountered in Australian installations. Read this as what you are likely to find, not as a selection guide — actual cable selection depends on current, run length, installation method, ambient temperature, grouping with other cables and the protective device.

SizeCommonly seen onTypical circuit
1.5 mm²Lighting circuits10 A
2.5 mm²General power outlets16–20 A
4 mm²Larger appliance circuits, some air conditioning20–25 A
6 mm²Ovens, single-phase EV chargers, long outlet runs32 A
10 mm²Submains to sheds and granny flats40–50 A
16 mm²Consumer mains, larger submains63 A+
25 mm²Consumer mains on larger installations80 A+
Do not size cable from a table like this. The same 6 mm² cable has a very different rating buried in soil, run in a wall cavity surrounded by insulation, or bunched with five other circuits in a conduit. Two circuits with identical current can legitimately need different cable. For anything connected to mains, cable selection is part of the licensed electrical work — and on long runs it is voltage drop, not current rating, that usually decides the answer.

How to Reduce Voltage Drop

ApproachEffectPracticality
Increase conductor sizeDrop is inversely proportional — double the mm², halve the dropUsually the first and easiest fix
Shorten the runDirectly proportional — half the length, half the dropRelocating a battery or sub-board is often cheaper than heavy cable
Raise system voltageHalves current, so halves drop and quarters power loss12 V → 24 V is transformative for off-grid
Split the loadLess current per cableTwo circuits instead of one long shared run
Copper instead of aluminiumAbout 38% less drop for the same sizeUsually already the case in small installations
Power loss is worse than the voltage figure suggests. The energy wasted in the cable is I²R, so it rises with the square of current. Double the current and cable losses quadruple. That is why halving current by doubling system voltage is such an effective move — and why the 20 A solar example above was heating the cable, not the battery.

Common Mistakes

  1. Treating a single-cable result as installation compliance. The 5% limit covers the whole path from the point of supply. A compliant cable can sit in a non-compliant installation.
  2. Entering the round-trip length. Enter the one-way distance. The formula already doubles it for the return path.
  3. Using the ×2 factor on three-phase circuits. Three phase uses √3, which is about 15.5% lower.
  4. Sizing on current capacity alone. On long runs, voltage drop governs cable size long before ampacity does. This is the classic solar and shed-supply error.
  5. Applying 5% to a 12 V system. That is only 0.6 V. Most 12 V design works to 3% or tighter.
  6. Ignoring temperature. Conductor resistance rises as the cable warms under load, so a hot cable drops more than a 20 °C calculation predicts.
  7. Forgetting connections. Corroded terminals, undersized lugs and poor crimps add resistance the calculation knows nothing about — and are a frequent cause of drop in older 12 V systems.

Frequently Asked Questions

What is voltage drop?

Voltage drop is the voltage lost along a cable because the conductor has resistance. The appliance at the far end receives less than the supply voltage. It is Ohm's Law applied to the cable itself: the drop equals the current multiplied by the cable's resistance.

How do you calculate voltage drop?

For DC and single-phase circuits: voltage drop = 2 × current × resistivity × one-way length ÷ conductor cross-section. Copper resistivity is about 0.0175 Ω·mm²/m. The 2 accounts for current travelling out and back. Three-phase circuits use √3 in place of 2.

How much voltage drop is allowed in Australia?

The AS/NZS 3000 Wiring Rules limit total voltage drop to 5% of nominal supply voltage from the point of supply to any point of utilisation — 11.5 V on a 230 V supply, 20 V on 400 V three phase. Critically, this is cumulative across consumer mains, submains and final subcircuits, not a per-cable allowance.

Does this calculator tell me if my installation complies?

No. It estimates the drop in one cable run at around 20 °C using resistance only. Compliance depends on the cumulative drop across the entire path, and formal assessment under AS/NZS 3008 uses tabulated values at the conductor's operating temperature that also account for reactance. Treat this as a design aid and have a licensed electrician verify any installation.

Does cable length affect voltage drop?

Directly and proportionally. Double the length and you double the drop. This is why long runs to sheds, pumps and outbuildings so often need cable far larger than the current alone would suggest — and why moving the source closer to the load can be cheaper than upsizing.

Does wire size affect voltage drop?

Inversely and proportionally. Doubling the conductor cross-section halves the drop, so moving from 4 mm² to 6 mm² reduces it by about a third. Increasing cable size is usually the simplest and most effective fix.

What cable should I use for a 12 V system?

Larger than most people expect, because 3% of 12 V is only 0.36 V. A 20 A load on 6 mm² copper exceeds 3% past roughly three metres one-way. Use the table above as a starting point, and consider whether 24 V or relocating the battery would serve you better than very heavy cable.

Why is voltage drop worse on 12 V than 230 V?

Two reasons compound. Delivering the same power at 12 V needs roughly nineteen times the current of a 230 V circuit, and drop is proportional to current. Then the percentage is measured against a much smaller number — a 0.5 V loss is 0.2% at 230 V but 4.2% at 12 V.

What is the difference between copper and aluminium for voltage drop?

Aluminium has roughly 61% higher resistivity, so for the same cross-section it drops about 61% more voltage. To match copper's performance you need roughly 1.6 times the cross-sectional area. Aluminium is lighter and cheaper per amp delivered, which is why it appears in large submains and overhead runs.

Does temperature affect voltage drop?

Yes. Copper's resistance rises with temperature, so a cable carrying its rated current runs hot and drops more than a 20 °C calculation suggests. Formal cable selection uses figures at the conductor's maximum operating temperature for exactly this reason, which is why tabulated values come out higher than a simple resistivity calculation.

How do I reduce voltage drop?

In rough order of effectiveness: increase the conductor size, shorten the run, raise the system voltage, or split the load across more than one circuit. Doubling conductor size halves the drop; doubling system voltage halves the current and therefore the drop as well, while quartering power loss in the cable.

Why does voltage drop waste energy?

The lost voltage becomes heat in the conductor. Power wasted equals current squared times cable resistance, so losses rise with the square of current — doubling current quadruples the waste. In a solar system, that is energy leaving the panels and never reaching the battery.

Size for the Drop, Not Just the Current

On short runs, current-carrying capacity decides cable size. On long ones — and on almost every 12 V system — voltage drop decides it first, usually by a wide margin. Checking both is the difference between a system that works and one that browns out under load.

From here, the Ohm's Law calculator covers the underlying relationships, the resistor calculator decodes component values, and the electricity cost calculator prices what those losses are costing you.

⚡ Electronics Calculators

Voltage Drop Calculator — cable losses and sizing (this page) Ohm's Law Calculator — volts, amps, ohms and watts Resistor Calculator — decode colour bands Electricity Cost Calculator — running cost from consumption

📋 References & Further Reading

Standards Australia — AS/NZS 3000 Wiring Rules and AS/NZS 3008 cable selection Safe Work Australia — Electrical safety Engineers Australia — Professional engineering standards International Electrotechnical Commission — International electrotechnical standards